SSFSDR-512
Combination Fire Smoke Dampers
Round Stainless Steel Blade
UL 555S Leakage Class II
UL555 1 1/2 Hour Fire Resistance Rating
Application
Model SSFSDR-512 is a combination fire smoke damper constructed
out of 304 stainless steel with 3 round style blade. The SSFSDR-512
has been qualified to 3000 fpm (15.2 m/s) and 4 in. wg (1 kPa) for
operation and dynamic closure in emergency fire smoke situations.
Model SSFSDR-512 may be installed vertically (with blades running
horizontal) or horizontally and is rated for airflow and leakage in
either direction.
Model SSFSDR-512 meets the requirements for
fire dampers, smoke dampers and combination fire
smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshall
Ratings
UL 555 Fire Resistance Rating
Fire Rating: 1 1/2 Hour
Dynamic Closure Rating: Actual ratings are size dependant
Maximum Velocity: 3000 fpm (15.2 m/s)
Maximum Pressure: 4 in. wg (1 kPa)
Listing #: 3225-0981:112 (fire)
Listing #: 3230-0981:113 (smoke)
UL 555S Leakage Rating
Leakage Class: II
“UL CLASSIFIED (see complete marking on
product)”
Operational Rating: Actual ratings are actuator dependant
Maximum Velocity: 3000 fpm (15.2 m/s)
Maximum Pressure: 4 in. wg (1 kPa)
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555 (Listing #R13317)
Maximum Temperature: 350º F (177°C) —Depending on actuator
Standard 555S (Listing #R13447)
Standard Construction
Frame/Sleeve: 20 ga. (1mm) 304 stainless steel round
integral sleeve
Blades: Double skin 304 stainless steel (14 ga.
[2mm] equivalent) round style blades
Seals: Extruded silicone rubber blade seals
Linkage: 304 stainless steel - concealed in jamb.
Axles: 1/2 in. (13mm) dia. 304 stainless steel.
Bearings: 304 stainless steel sleeve type
Fusible Link: UL listed 165ºF (74ºC) -not 304SS
Size Limitations
Minimum Size: 6 in. (152mm) diameter
Maximum Size: 24 in. (610mm) diameter
Optional Features
• OCI (Open closed indication switches) -not 304SS
• 165º F (74°C), 212º F (100°C), and 350º F (177°C) RRL available
- not 304SS.
• TOR (remote override of 165º F (74°C) closure allows damper to
perform smoke management functions during a fire emergency)
- not 304SS.
D*
• Electric or pneumatic actuators to accomplish smoke management
and system functions.
* Dimensions furnished approximately 1/8 in. (3mm) undersize.
• One retainer plate required, additional retainer plate available.
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve
Opening + 2 in. Min.
Nut
Retaining
Plate Assembly
Clamping
Minimum Wall/Floor Opening
Screw
= Nominal Dia. + 7/8 in.
1.00 in. Min. Typ.
Clamping Screw
Fasteners
|
Grizzly Sander G0677 User Manual
Grizzly Welder H8153 User Manual
Grundig Flat Panel Television 32 VLC 6121 C User Manual
Honeywell Portable Generator 6065 User Manual
Hotpoint Range RA720 User Manual
HP Hewlett Packard Welder ML 150 G3 User Manual
Hunter Fan Fan 21618 User Manual
Hunter Fan Outdoor Ceiling Fan 21583 User Manual
Husqvarna Snow Blower 1130SB LS User Manual
i mate PDAs Smartphones PDA2 User Manual